Refrigerant leak shutdown - multi-zone

D5FSFA

What is going on

The outdoor unit shuts off, the emergency shutoff valve closes, all EEVs close, and all indoor units run at turbo fan speed. The unit detecting the leak shows EHC1 or EHC2. Other indoor units show ECC1.

Check in this order

  1. Once the leak drops below the LFL threshold, the audible alarm resets after 2 minutes and error codes clear after 5 minutes.
  2. The shutoff valve opens automatically after 2.5 hours.
  3. To bypass the valve time lock, press and hold the point check button on the MZU for 10 seconds, only if no leak is detected.
  4. Power cycling the MZU does not reset the time lock.

Applies to: Multi-zone systems

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FSFAH service manual, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.