Carrier · Mini-split troubleshooting
Refrigerant leak sensor response (indoor leakage sensor)
What is going on
On detection of a leak the outdoor unit shuts off, indoor fan runs turbo, louvers fully open, and an audible alarm sounds. In single-zone systems the alarm resets after 2 minutes below LFL and the code clears after 5 minutes. Power cycling the outdoor unit for 5 minutes resets alarm and code. In multi-zone systems the emergency shutoff valve closes, all EEVs close, and the valve reopens automatically after 2.5 hours once the leak is below LFL.
Likely causes
- Refrigerant leak detected at indoor unit
- Leak sensor out of range
Check in this order
- Identify the indoor unit showing EH C1 or EH C2.
- Locate and repair the refrigerant leak before restarting.
- Single zone after the leak is gone, wait for the clear time or power cycle the outdoor unit for 5 minutes.
- Multi-zone the shutoff valve time-lock can be bypassed by holding the check button in the MZU for 10 seconds, only when no leak is detected. Power cycling the MZU does not reset the time-lock.
Applies to: D5FCFAH
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FCFAH service manual, p. 20. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.