Refrigerant leak sensor response (indoor leakage sensor)

D5FCFA

What is going on

On detection of a leak the outdoor unit shuts off, indoor fan runs turbo, louvers fully open, and an audible alarm sounds. In single-zone systems the alarm resets after 2 minutes below LFL and the code clears after 5 minutes. Power cycling the outdoor unit for 5 minutes resets alarm and code. In multi-zone systems the emergency shutoff valve closes, all EEVs close, and the valve reopens automatically after 2.5 hours once the leak is below LFL.

Likely causes

  • Refrigerant leak detected at indoor unit
  • Leak sensor out of range

Check in this order

  1. Identify the indoor unit showing EH C1 or EH C2.
  2. Locate and repair the refrigerant leak before restarting.
  3. Single zone after the leak is gone, wait for the clear time or power cycle the outdoor unit for 5 minutes.
  4. Multi-zone the shutoff valve time-lock can be bypassed by holding the check button in the MZU for 10 seconds, only when no leak is detected. Power cycling the MZU does not reset the time-lock.

Applies to: D5FCFAH

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FCFAH service manual, p. 20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.