Refrigerant leak detected (units with sensor)

D5FSOAH

What is going on

On units with a refrigerant sensor, a detected leak makes the indoor unit show an error code and buzz. The outdoor compressor stops right away and the indoor fan runs.

Likely causes

  • Refrigerant leak at a joint or line set
  • Refrigerant sensor detected leaked refrigerant

Check in this order

  1. Expect the indoor unit to show an error code and buzz; the outdoor compressor stops and the indoor fan keeps running.
  2. Keep the unit powered except during service.
  3. Remove or extinguish all open flames before searching for the leak.
  4. Find the leak with an electronic detector rated 1/8 oz (5 g) per year or better, or with leak detection fluid.
  5. Recover refrigerant from the system or isolate the leaking section with shut-off valves before any brazing.

Applies to: Units with refrigerant sensor, R-454B

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FSOAH installation manual, p. 5-6. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.