Refrigerant leak detected by sensor
What is going on
When the leak sensor detects refrigerant, the indoor unit shows an error code and buzzes, the outdoor compressor stops immediately, and the indoor fan keeps running.
Likely causes
- Refrigerant leak in the refrigerant circuit or at field joints
Check in this order
- Remove or extinguish all open flames and ignition sources.
- Ventilate the area and keep any mechanical ventilation openings clear.
- Locate the leak with an approved electronic detector (1/8 oz/5 g per year sensitivity) or a bubble/fluorescent leak detection fluid. Do not use a halide torch or naked flame.
- If brazing is needed, recover all refrigerant first or isolate that section with shut-off valves.
Applies to: Units with refrigerant leak sensor, R454B flammable refrigerant
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FSHA installation manual, p. 5-6. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.