Carrier · Mini-split troubleshooting

Refrigerant leak detected by indoor unit sensor

D5FCFA

What is going on

On units with a refrigerant sensor, a detected leak makes the indoor unit show an error code and buzz. The outdoor compressor stops straight away and the indoor fan keeps running. The sensor life is 15 years.

Likely causes

  • Refrigerant leak in the refrigerant circuit

Check in this order

  1. Keep the area open or well ventilated before breaking into the system or doing any hot work.
  2. Remove all naked flames and ignition sources from the area.
  3. Find the leak with an electronic detector suitable for flammable refrigerant, or with a bubble/fluorescent leak detection fluid. Never use a halide torch or any naked flame detector.
  4. If brazing is needed, recover all refrigerant or isolate the leaking section with shut-off valves first.
  5. Keep a dry powder or CO2 fire extinguisher near the charging area when hot work is done.

Applies to: Indoor units with refrigerant sensor, flammable refrigerant (R-454B)

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FCFA installation manual, p. 3 and p. 5. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.