Carrier · Mini-split troubleshooting

Recovering and decommissioning a flammable refrigerant system

D5FSCAH / D5FLCAH

What is going on

Only competent, certified technicians should decommission. Oil and refrigerant samples should be taken first if reuse may be needed.

Check in this order

  1. Make sure electrical power is available and isolate the system electrically.
  2. Take oil and refrigerant samples before recovery if analysis may be needed.
  3. Pump down the system if possible. If not, fit a manifold to recover from several points.
  4. Keep the recovery cylinder on scales and do not fill it above 80% liquid volume.
  5. Do not exceed the cylinder maximum working pressure.
  6. Remove the cylinders and equipment promptly and close all isolation valves.
  7. Do not charge recovered refrigerant into another system unless it has been cleaned and checked.
  8. Label the equipment as decommissioned and emptied, dated and signed, and show that it contains flammable refrigerant.

Applies to: Decommissioning R454B equipment

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FSCAH / D5FLCAH service manual, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.