Recovering and decommissioning a flammable refrigerant system
What is going on
Only competent, certified technicians should decommission. Oil and refrigerant samples should be taken first if reuse may be needed.
Check in this order
- Make sure electrical power is available and isolate the system electrically.
- Take oil and refrigerant samples before recovery if analysis may be needed.
- Pump down the system if possible. If not, fit a manifold to recover from several points.
- Keep the recovery cylinder on scales and do not fill it above 80% liquid volume.
- Do not exceed the cylinder maximum working pressure.
- Remove the cylinders and equipment promptly and close all isolation valves.
- Do not charge recovered refrigerant into another system unless it has been cleaned and checked.
- Label the equipment as decommissioned and emptied, dated and signed, and show that it contains flammable refrigerant.
Applies to: Decommissioning R454B equipment
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FSCAH / D5FLCAH service manual, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.