Daikin · Mini-split troubleshooting
Recover refrigerant and decommission the unit
What is going on
Recovery and decommissioning steps for R-32 units. Take an oil and refrigerant sample first if the recovered refrigerant may be reused.
Check in this order
- Isolate the system electrically.
- Pump down the system if vacuum can be ensured. If not, use a manifold to recover from several points.
- Set the recovery cylinder on a calibrated scale before recovery.
- Do not fill cylinders above 80% of liquid volume.
- Do not exceed the cylinder's maximum working pressure, even briefly.
- Use recovery equipment rated for R-32 with leak-free couplings.
- Never mix refrigerants in recovery units or cylinders.
- Do not recharge recovered refrigerant into another system until it has been cleaned and checked.
- Label the unit as decommissioned and emptied, dated and signed, and show that it contains R-32.
- Before removing compressor oil, evacuate the refrigerant dissolved in it. Heat only the compressor body electrically to speed this up.
Applies to: Decommissioning and refrigerant recovery, R-32
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTXM-W/V service manual, pp. 12-13. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.