Daikin · Mini-split troubleshooting

Recover refrigerant and decommission the unit

FTXM-W/V

What is going on

Recovery and decommissioning steps for R-32 units. Take an oil and refrigerant sample first if the recovered refrigerant may be reused.

Check in this order

  1. Isolate the system electrically.
  2. Pump down the system if vacuum can be ensured. If not, use a manifold to recover from several points.
  3. Set the recovery cylinder on a calibrated scale before recovery.
  4. Do not fill cylinders above 80% of liquid volume.
  5. Do not exceed the cylinder's maximum working pressure, even briefly.
  6. Use recovery equipment rated for R-32 with leak-free couplings.
  7. Never mix refrigerants in recovery units or cylinders.
  8. Do not recharge recovered refrigerant into another system until it has been cleaned and checked.
  9. Label the unit as decommissioned and emptied, dated and signed, and show that it contains R-32.
  10. Before removing compressor oil, evacuate the refrigerant dissolved in it. Heat only the compressor body electrically to speed this up.

Applies to: Decommissioning and refrigerant recovery, R-32

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTXM-W/V service manual, pp. 12-13. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.