Carrier · Mini-split troubleshooting
R-454B (A2L flammable refrigerant) field piping, leak test and charging requirements
What is going on
Requirements for field-made refrigerant work on this A2L flammable refrigerant system. Only trained and certified service personnel should work on the refrigerant circuit.
Check in this order
- Only use technicians with a current, valid refrigerant handling certificate.
- Keep field piping as short as practical and protect it from physical damage.
- Pressure test the field piping with inert gas, then vacuum test before charging.
- Hold the test pressure for at least 1 hour with no pressure drop on the gauge. Gauge resolution must not exceed 5% of test pressure.
- During evacuation, the pressure must not rise above 1500 microns within 10 minutes after isolating the pump. The vacuum target is the lesser of 500 microns or the local code value.
- Tightness test field-made indoor joints at at least 125% of maximum allowable pressure with a detector sensitivity of 1/8 oz (5 g)/year. No leak allowed.
- Do not use open flames or halide torches to search for leaks. Use a leak detector suitable for flammable refrigerants, or a bubble or fluorescent leak detection fluid.
- Purge the system with oxygen-free nitrogen. Do not use compressed air or oxygen.
- Charge by the liquid method. Do not overfill. Pressure test with OFN before recharging.
- Label the system as containing flammable refrigerant after charging is complete.
Applies to: Field refrigerant piping, joints, evacuation and charging
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FSOAH Owner's Manual, pp. 2-5. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.