Carrier · Mini-split troubleshooting

Pressure test and evacuation of field refrigerant piping

D5FSOAH

What is going on

Field piping must be pressure tested with inert gas and vacuum tested before charging.

Check in this order

  1. Pressure test the field piping with nitrogen to 500 psi.
  2. Remove the pressure source and hold the pressure for at least 1 hour. The gauge must show no drop; gauge resolution must not exceed 5% of test pressure.
  3. Evacuate the system. Once it reaches the required vacuum level, isolate the pump.
  4. Confirm the pressure does not rise above 1500 microns within 10 minutes.
  5. Use a vacuum of 500 microns or less, or the level required by local code if that is stricter.
  6. Test field joints indoors at 125% of maximum allowable pressure with sensitivity of 1/8 oz (5 g) per year; no leak allowed.

Applies to: Split systems, field-made piping

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FSOAH installation manual, p. 5. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.