Pressure and vacuum test of field piping
What is going on
Test field piping after install and before charging. The tightness test for indoor joints uses a sensitivity of 5 g/year.
Check in this order
- Pressure test field piping with inert gas. Use the low side design pressure for the low side and the high side design pressure for the high side. If the sides cannot be isolated, test the whole system to the low side design pressure.
- Hold the test pressure for at least 1 hour with no drop on the gauge. Gauge resolution must not exceed 5% of test pressure.
- Evacuate the system. Isolate from the pump and confirm the pressure does not rise above 1500 microns within 10 minutes.
- Use the vacuum level in the manual, which is the lower of 500 microns or the local code value.
- Test indoor field joints with a method of 5 g/year sensitivity or better at no less than 0.25 times the maximum allowable pressure. No leak is allowed.
Applies to: Field-made refrigerant piping
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FSCAH / D5FLCAH service manual, p. 6. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.