Daikin · Mini-split troubleshooting
Pre-trial-run installation checks
What is going on
Check each item before the trial run. The listed symptom is what happens if the item is missed.
Likely causes
- Units not secured: fall, vibration, noise
- Refrigerant leak: incomplete cooling or heating
- Refrigerant and drain hose insulation missing: water leakage
- Drain line not installed correctly: water leakage
- Unit not grounded: electrical leakage
- Wrong wires or wrong connections: no operation or burn damage
- Air inlet or outlet blocked on either unit: incomplete cooling or heating
- Stop valves not open: incomplete cooling or heating
- Remote controller not reaching indoor unit: no operation
- SSID sticker with release paper not given to user: wireless LAN cannot connect
Check in this order
- Confirm indoor and outdoor units are secured.
- Check for refrigerant leaks.
- Confirm refrigerant gas and liquid pipes and drain hose extension are insulated.
- Confirm the drain line is correctly installed.
- Confirm the system is properly grounded.
- Confirm only specified wires are used and all are connected correctly.
- Confirm no air inlet or outlet is obstructed on either unit.
- Open both stop valves.
- Confirm the indoor unit receives remote controller commands.
- Give the SSID sticker with release paper to the user.
Applies to: FTXM-W/V installs before trial operation
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SiUS042113EA Inverter Pair service manual, p. 163. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.