Carrier · Mini-split troubleshooting
Power and communication wiring between indoor and outdoor units
What is going on
Power and communication run from the outdoor unit to the indoor unit as four conductors. The wiring is polarity sensitive.
Check in this order
- Use 14/3 stranded wire with ground, 600 V rated, for the outdoor-to-indoor run.
- Do not use BX cable.
- Keep polarity correct on all connections.
- In a high EMF area with communication faults, use 14/2 stranded shielded wire for L2 and S; land the shield to ground at the outdoor unit only.
- Size all wire per NEC/CEC and local code using the MCA and MOP values.
- Tighten every terminal; loose connections can overheat.
- Keep wires away from refrigerant tubing, the compressor and moving parts.
- Provide a disconnect within sight of and readily accessible from the unit.
Applies to: Indoor and outdoor unit field wiring
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FSOA Product Data, p. 12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.