Post-repair electrical and drainage checks

FTXM-W/V

What is going on

Checks to finish with before handing the unit back.

Check in this order

  1. Measure insulation resistance after the repair. It must be 1 MΩ or higher.
  2. Check the earth/grounding and fix it if the unit is not properly grounded.
  3. Check that all wiring connections, including soldered and crimped terminals, are secure.
  4. Check that the terminal cover is fitted so the inter-unit cable cannot lift it off.
  5. Check the indoor unit drain after the repair.
  6. Check for refrigerant leaks after charging.

Applies to: All repairs before return to service

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTXM-W/V service manual, pp. 9, 14-15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.