Carrier · Mini-split troubleshooting
Opening the refrigerant circuit for repair
What is going on
Sequence for breaking into a flammable refrigerant circuit.
Check in this order
- Remove the refrigerant safely according to local and national rules.
- Evacuate the system.
- Purge the circuit with inert gas. This is optional for A2L refrigerants.
- Evacuate again. This is optional for A2L refrigerants.
- If a flame will be used to open the circuit, keep flushing with inert gas while cutting.
- Open the circuit.
- Purge with oxygen-free nitrogen only. Never use compressed air or oxygen.
- Repeat the nitrogen purge as needed, then vent to atmospheric pressure before work starts.
- Keep the vacuum pump outlet away from ignition sources and make sure there is ventilation.
Applies to: D5FSCAH / D5FLCAH
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FSCAH/D5FLCAH service manual, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.