Carrier · Mini-split troubleshooting

Opening the refrigerant circuit for repair

D5FSCAHD5FLCAH

What is going on

Sequence for breaking into a flammable refrigerant circuit.

Check in this order

  1. Remove the refrigerant safely according to local and national rules.
  2. Evacuate the system.
  3. Purge the circuit with inert gas. This is optional for A2L refrigerants.
  4. Evacuate again. This is optional for A2L refrigerants.
  5. If a flame will be used to open the circuit, keep flushing with inert gas while cutting.
  6. Open the circuit.
  7. Purge with oxygen-free nitrogen only. Never use compressed air or oxygen.
  8. Repeat the nitrogen purge as needed, then vent to atmospheric pressure before work starts.
  9. Keep the vacuum pump outlet away from ignition sources and make sure there is ventilation.

Applies to: D5FSCAH / D5FLCAH

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FSCAH/D5FLCAH service manual, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.