Carrier · Mini-split troubleshooting
Opening the refrigerant circuit and recharging (flammable refrigerant R-454B)
What is going on
Only trained and certified technicians may open the refrigerant circuit. Make sure the area is ventilated and there are no ignition sources before working.
Check in this order
- Recover the refrigerant into the correct recovery cylinders.
- Evacuate the system.
- Purge the circuit with oxygen-free nitrogen, then evacuate again.
- Use nitrogen flushing if you cut open the circuit with a flame.
- Open the circuit.
- Do not use compressed air or oxygen to purge.
- Use only suitable tools and keep charging hoses as short as possible.
- Ground the refrigeration system before charging.
- Charge by the liquid method and take care not to overfill.
- Pressure test with oxygen-free nitrogen before recharging.
- Leak test after charging and before commissioning, then leak test again before leaving the site.
- Label the system when charging is complete.
Applies to: D5FSHAH systems using R-454B
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FSHAH Owner's Manual, p. 4. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.