Daikin · Mini-split troubleshooting

Open an R-32 refrigerant circuit safely

FTXM-W/V

What is going on

Follow this order whenever the refrigerant circuit must be broken for a repair.

Check in this order

  1. Recover the refrigerant into correct recovery cylinders.
  2. Purge the circuit with inert gas (OFN).
  3. Evacuate the inert gas.
  4. Purge again with inert gas.
  5. Cut or braze the circuit.
  6. Flush the system with OFN by filling to working pressure, venting to atmosphere, and pulling vacuum again. Repeat until no refrigerant remains.
  7. Vent the system to atmospheric pressure before brazing.
  8. Never use compressed air or oxygen for flushing.
  9. Keep the vacuum pump outlet away from ignition sources and ventilated.

Applies to: R-32 refrigerant circuit repair, brazing or cutting

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTXM-W/V service manual, p. 11. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.