Mark the mounting plate and wall hole
What is going on
The wall hole size depends on the gas-side pipe size. A gas line of 5/8 in (16 mm) or larger needs a 3.54 in (90 mm) hole. A gas line smaller than 5/8 in (16 mm) needs a 2.5 in (65 mm) hole. The mounting plate has a bubble level that cannot be removed.
Check in this order
- Remove the screw that holds the mounting plate to the back of the indoor unit.
- Fasten the mounting plate to the wall with the supplied screws, keeping it flat against the wall.
- Check the bubble level on the plate and keep the plate level.
- Use the plate ruler to locate the wall hole based on the plate position.
- For brick or concrete walls, drill 0.2 in (5 mm) holes and install the supplied sleeve anchors before tightening the plate screws.
- If the plate level bubble breaks, clean up any leaking liquid.
Applies to: Indoor unit mounting plate, D5FSHA 6K to 36K
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FSHA installation manual, p. 15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.