Carrier · Mini-split troubleshooting

Leak detection on flammable refrigerant systems

D5FSCAH / D5FLCAH

What is going on

Do not use a naked flame to find leaks. Electronic detectors may need recalibration for flammable refrigerants.

Check in this order

  1. Do not use a halide torch or any detector with a naked flame.
  2. Use an electronic detector suited to the refrigerant and calibrated in a refrigerant-free area; set the alarm at no more than 25% of the LFL.
  3. Use bubble or fluorescent leak detection fluid if needed; avoid chlorine-based detergents.
  4. If a leak is found that needs brazing, recover the refrigerant or isolate that section with valves first.

Applies to: Refrigerant leak search

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FSCAH / D5FLCAH service manual, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.