Leak checking a system with flammable refrigerant

D5FSCAHD5FLCAH

What is going on

Find refrigerant leaks without any ignition source on a flammable refrigerant system.

Check in this order

  1. Never use a halide torch or any open-flame detector.
  2. Use an electronic leak detector rated for the refrigerant. Calibrate it in a refrigerant-free area and confirm it is set to no more than 25% of the LFL.
  3. Use leak detection fluids for a bubble or fluorescent check. Do not use chlorine-based detergents.
  4. If a leak is suspected, remove or put out all open flames first.
  5. If the leak needs brazing, recover the refrigerant or isolate that part of the system with shut-off valves before working on it.

Applies to: D5FSCAH / D5FLCAH

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FSCAH/D5FLCAH service manual, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.