Carrier · Mini-split troubleshooting

IPM continuity check

D5FSFA

What is going on

Checks the IPM module by measuring diode-type resistance between the module terminals. Electricity can stay in the capacitors after power-off, so discharge them first.

Check in this order

  1. Turn off the outdoor unit and disconnect the power supply.
  2. Discharge the electrolytic capacitors and make sure all stored energy is gone.
  3. Disassemble the outdoor PCB or the IPM board.
  4. Measure resistance between P and U, V, W and N, and between U, V, W and N as shown in Fig. 25.
  5. Compare readings with Table 7; the table values are not legible in the text, so use the manual's Table 7 directly.

Applies to: D5FSFAH outdoor unit IPM module

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FSFAH service manual, p. 36. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.