Carrier · Mini-split troubleshooting

Install the indoor drain line

D5FSOAH

What is going on

Set up the drain so water runs away from the unit and cannot flow back. In HEAT mode the outdoor unit also discharges water, so keep the hose where it will not cause damage or a slip hazard.

Check in this order

  1. Connect the drain pipe to the indoor unit with the drain adapter.
  2. Slope the drain pipe downward at least 1/100 along its whole length.
  3. Hang supports every 39-59 in (1-1.5 m) so the pipe does not sag.
  4. If the drain outlet is higher than the pump joint, add a lift pipe no higher than 29.5 in (75 cm) from the ceiling board and less than 11.8 in (30 cm) from the unit.
  5. Keep the hose level or tilted up no more than 3 in (75 mm) to avoid air bubbles.
  6. Insulate all drain piping to prevent condensation.
  7. Use a metal clamp or protection tube on extended drain pipe so it cannot pull loose.
  8. Do not pull the drain pipe hard. Bent or badly installed pipe can cause a water level switch fault.
  9. Run the outlet to a safe spot, at least 1.9 in (50 mm) above ground. If discharging to a sewer, use a U or S trap.

Applies to: Indoor unit drainage, 6K-18K

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FSOAH installation instructions, p. 17-18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.