Carrier · Mini-split troubleshooting

Indoor units mode conflict (multi outdoor unit match)

D5FSFAH

What is going on

Indoor units cannot run COOLING and HEATING at the same time; HEATING takes priority. If one indoor unit is in COOLING or FAN and another is set to HEATING, the cooling or fan unit powers off and the heating unit keeps running. If one unit is heating and another is set to COOLING or FAN, the cooling or fan unit goes to STANDBY and the heating unit does not change. Conflict matrix (Table 9): COOLING vs HEATING = conflict; COOLING vs FAN = no conflict; COOLING vs OFF = no conflict; HEATING vs FAN = conflict; HEATING vs OFF = no conflict; FAN vs OFF = no conflict; all other pairs = no conflict.

Applies to: D5FSFAH indoor units connected to a multi outdoor unit

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FSFAH service manual, p. 48. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.