Carrier · Mini-split troubleshooting
Indoor unit mounting height and room limits
What is going on
Height and room size requirements for R-454B units.
Check in this order
- Mount the indoor unit at least 7.6 ft (2.3 m) above the floor.
- Room height must be at least 7.3 ft (2.2 m).
- Check the minimum room area in the refrigerant charge table for the actual charge and mounting height.
Applies to: R-454B indoor units
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FSOAH installation manual, p. 4. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.