Daikin · Mini-split troubleshooting
Indoor fan speed control (automatic fan setting)
What is going on
Fan has 9 steps: LLL, LL, SL, L, ML, M, MH, H and HH (HH is POWERFUL). With FAN set to automatic, the airflow is chosen from the gap between room thermistor temperature and target temperature, and step SL is not used. In cooling, the fan's upper limit is M tap for the first 30 minutes after start. In heating, the fan speed also depends on indoor coil temperature. The fan stops during defrost.
Check in this order
- Check the FAN setting; automatic mode gives the speed range described above.
- In cooling, expect fan to be capped at M tap for the first 30 minutes.
- In heating, expect fan to stop during defrost.
- If fan speed seems wrong, compare room thermistor reading with target temperature before replacing parts.
Applies to: FTXM-W/V indoor unit, automatic fan speed
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SiUS042113EA service manual, p. 41. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.