High pressure protection control

FTXM-W/V

What is going on

To avoid tripping the high pressure safety device, the control acts when high pressure safety (HPS) reaches 4.15 MPa or more while the compressor is on. The compressor stops and shows E3. If it stops 4 times within 60 seconds, the unit makes an abnormal stop and keeps the E3 indication. Heating peak-cut control works alongside this function.

Likely causes

  • High pressure reaching 4.15 MPa or more with the compressor running
  • Four high-pressure stops within 60 seconds

Check in this order

  1. Check whether the unit shows a normal stop or an abnormal stop (E3 kept).
  2. Review the high pressure switch actuation section of the manual for further checks.

Applies to: Heating and cooling operation, outdoor unit

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTXM-W/V service manual, p. 81. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.