Daikin · Mini-split troubleshooting

Heating peak-cut control

FTXM-W/V

What is going on

In heating, the indoor heat exchanger temperature sets the compressor frequency upper limit to prevent abnormally high pressure. Stop zone: compressor stops. Dropping zone: frequency upper limit decreases. Keep zone: upper limit held. Up zone: upper limit increases. Reset zone: upper limit cancelled.

Check in this order

  1. Read the indoor heat exchanger temperature (R2T) and find the zone.
  2. Compare with the heating peak-cut zone reference table in this section.

Applies to: Heating operation, FTXM-W/V wall mounted units

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTXM-W/V service manual, p. 80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.