Daikin · Mini-split troubleshooting
H8 check flow (DC voltage/current sensor)
What is going on
Flowchart for H8. Some branch text in the page scan is out of order, so follow the decision points as listed here and check the referenced checks (No.15 and No.21) in the full manual.
Likely causes
- Power supply voltage outside range
- Capacitor voltage not rising with frequency
- Compressor wiring or compressor fault
- Defective outdoor unit PCB
Check in this order
- Turn the power off, then back on to restart the system, and start operation.
- If the error returns, check the capacitor voltage. It should be charged when the indoor or outdoor main relay turns on, and rise with frequency.
- Measure the rectifier input voltage. It should be within 320 VDC.
- Check that the power supply voltage is within the allowed range (supply voltage plus or minus 15%). Correct the supply or replace the outdoor PCB as needed.
- Use the inverter analyzer (RSUK0917C) to check running current against the guideline, and check that no LED is off and the compressor is running.
- Turn the power off, disconnect harnesses U, V and W, then reconnect them, power on and restart operation to check for wiring faults.
- If the current is still wrong, replace the compressor or the outdoor unit main PCB as the check directs.
Applies to: Outdoor unit, H8 error
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin Inverter Pair Wall Mounted FTXM-W/V service manual, p. 137. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.