Daikin · Mini-split troubleshooting
Freeze-up protection control (cooling)
What is going on
In cooling, the signal from the indoor unit sets the compressor frequency upper limit so the indoor heat exchanger does not freeze. The signal is split into zones, and the frequency limit is judged from the indoor heat exchanger temperature.
Check in this order
- Read the indoor heat exchanger temperature and check which zone it falls in.
- Expect the frequency upper limit to be reduced when the indoor coil is in a lower zone.
Applies to: Cooling operation, FTXM-W/V wall mounted units
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTXM-W/V service manual, p. 80. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.