Carrier · Mini-split troubleshooting
Field wiring between indoor and outdoor units
What is going on
Power and communication run between the indoor and outdoor units. The main power feeds the outdoor unit, and the link to the indoor unit carries power and communication.
Check in this order
- Size all wire per NEC or CEC and local codes, using the MCA and MOCP values from the electrical data table.
- Use only stranded copper conductors rated 600 V.
- Use 14/3 stranded wire with ground for the power and communication link (four conductors total: two line/neutral, one communication S, one ground).
- Keep the wiring polarity correct between the indoor and outdoor units.
- Do not use BX cable.
- In high EMF areas with communication problems, use 14/2 stranded shielded wire for L2/N and S. Land the shield to ground at the outdoor unit only.
- Tighten every connection and keep wires away from refrigerant tubing, compressor and moving parts.
- Provide a disconnect within sight of and readily accessible from the unit.
Applies to: D5FSHA indoor and outdoor units
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FSHA product data, p. 9. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.