Carrier · Mini-split troubleshooting

Fan speed out of control protection

D5FCFA

What is going on

Indoor fan below 300 RPM for 50 seconds shuts the fan off and it restarts 30 seconds later. After three restarts the unit stops and the LED shows the failure. Outdoor fan below 100 RPM or above 1500 RPM for 60 seconds stops the unit, the LED shows the failure, and the fault clears 30 seconds later.

Likely causes

  • Indoor fan motor or speed feedback problem
  • Outdoor fan motor or speed feedback problem

Check in this order

  1. Check the indoor fan motor and its speed signal when the indoor fan drops below 300 RPM.
  2. Check the outdoor fan motor and its speed signal when the outdoor fan is below 100 RPM or above 1500 RPM.
  3. Confirm fan motor wiring and connectors are secure.

Applies to: D5FCFAH

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FCFAH service manual, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.