Fan motor check (indoor DC motor and outdoor DC motor)
What is going on
Checks for DC fan motors. Indoor motors have the control chip inside the motor. Outdoor motors have the control chip on the outdoor PCB.
Check in this order
- Indoor DC motor with power on and the unit in standby, measure voltage at pin 1 to pin 3 and pin 4 to pin 3 on the fan motor connector. If not in range (see table), replace the PCB.
- Outdoor DC motor release the UVW connector. Measure resistance U-V, U-W and V-W.
- If the three resistances are not equal, replace the fan motor.
- If they are equal, replace the outdoor PCB.
Applies to: D5FSOAH indoor and outdoor fan motors
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FSOAH service manual, p. 31. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.