Carrier · Mini-split troubleshooting
Fan and motor removal (indoor console unit)
What is going on
Disassembly sequence for the indoor fan and fan motor on the D5FCFAH console unit.
Check in this order
- Remove the fixing screw of the supporting board.
- Remove the screws of the fan motor support, then remove the ground wire screw.
- Remove the two screws holding the fan motor shaft.
- Release the hooks of the volute shell and lift it off.
- Remove the three fan screws and take out the fan.
Applies to: D5FCFAH console ductless system, sizes 18K to 60K
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FCFAH service manual, p. 56-58. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.