Carrier · Mini-split troubleshooting

Evaporator removal (indoor console unit)

D5FCFA

What is going on

Disassembly sequence for the indoor evaporator, including the sensor, water collector and stepper motor.

Check in this order

  1. Remove the screws of the left and right panels, then slide the panel in the direction shown to move it.
  2. Remove the nine screws of the front panel.
  3. Remove the one screw of the water collector.
  4. Remove the three screws of the board, then remove the board.
  5. Remove the screws of the pipe clamp board.
  6. Pull up the temperature sensor.
  7. Remove the screws of the front evaporator support.
  8. Remove the four screws of the rear evaporator support, then pull out the evaporator.
  9. Remove the two screws and remove the stepper motor.

Applies to: D5FCFAH console ductless system, sizes 18K to 60K

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FCFAH service manual, p. 59-62. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.