Daikin · Mini-split troubleshooting

Dry operation: room temperature zones, fan and expansion valve control

FTXM-W/V

What is going on

In dry mode the room temperature zone sets the fan tap. Airflow cannot be set manually, and fan speed also responds to room humidity. Fan speeds in dry mode differ from cooling mode. The electronic expansion valve controls indoor evaporating temperature so the liquid pipe thermistor near the valve outlet reaches its target.

Check in this order

  1. Confirm the room temperature at dry start to pick the zone.
  2. Use the thermostat ON/OFF offsets in the dry operation table.
  3. Expect fan speed to be automatic; do not look for a manual airflow setting.
  4. For dry-mode refrigerant control checks, read the liquid pipe thermistor near the expansion valve outlet against its target.

Applies to: FTXM-W/V in DRY mode

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SiUS042113EA service manual, pp. 43-44. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.