Drill the wall penetration

D5FSOAH

What is going on

Make a sloped wall hole so the drain and piping leave with proper fall.

Check in this order

  1. Avoid wires and plumbing in the wall before drilling.
  2. Drill with a 2.5 in (65 mm) core drill, or a 3.54 in (90 mm) core drill if the gas line is 5/8 in (16 mm) or larger.
  3. Drill with a slight downward angle so the outdoor end is about 0.2-0.275 in (5-7 mm) lower than the indoor end.
  4. Place the protective wall cuff in the hole to protect the edges and help seal it at the end of installation.
  5. Pass the drain hose through the hole so water drains to a safe location.

Applies to: Wall penetration for indoor/outdoor piping and drain

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FSOAH installation instructions, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.