Drill the wall hole for piping
What is going on
The hole must slope so the outdoor end is lower than the indoor end. This lets condensate drain outward. Avoid wires, plumbing and other sensitive parts while drilling.
Check in this order
- Use a 2.5 in (65 mm) or 3.54 in (90 mm) core drill, matched to the pipe size.
- Drill at a slight downward angle so the outdoor end is about 0.2-0.275 in (5-7 mm) lower than the indoor end.
- Insert the protective wall cuff into the hole to protect the edges and help seal it.
- Check the drilled area for wires, plumbing and other sensitive components before drilling.
Applies to: Wall hole for D5FSHA piping
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FSHA installation manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.