Carrier · Mini-split troubleshooting
Drill the wall hole and set the drain route
What is going on
Route the drain so water flows away from the unit with no sagging.
Check in this order
- Choose the wall hole position based on the outdoor unit location.
- Drill with a 2.5 in (65 mm) or 3.54 in (90 mm) core drill, angled down so the outdoor end is about 0.5 in (12 mm) lower than the indoor end.
- Set the protective wall cuff in the hole.
- Avoid wires, plumbing and sensitive components when drilling.
- Slope the drain at least 1/8 in per foot (2.5 cm per 30 cm) so water does not flow back into the unit.
- Hang the drain line every 39-59 in (1-1.5 m) to prevent sagging.
- Keep the drain outlet at least 1.9 in (50 mm) above the ground.
- If draining into a sewer, use a U or S trap to block odors.
Applies to: Indoor unit condensate drain installation
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FCFA installation manual, p. 18-19. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.