Carrier · Mini-split troubleshooting

Display shows a strange code or does not answer the remote - DLFSHB indoor

Carrier DLFSHB high wall indoor

What is going on

The indoor display on a Carrier DLFSHB high wall unit shows something that is not in the code tables, or the unit does not answer the remote. Before replacing any board, confirm what you are looking at, because a plain temperature readout is often taken for a fault. Switch power off before opening the cover or handling any boards.

Likely causes

  • Temperature reading mistaken for a fault code
  • Bad indoor PCB
  • Bad display board

Check in this order

  1. Confirm the displayed characters are not just a temperature reading.
  2. Test with the remote. Display works but the unit ignores the remote means the indoor PCB should be replaced.
  3. Unit responds but the display stays dark after pressing LED means the display board should be replaced.
  4. With power off, reseat the display and PCB connectors and look for damaged pins before ordering parts

Applies to: DLFSHBH high wall indoor units 09-24K (Midea / Carrier / Viessmann) on DLC multi-zone or single-zone outdoor units

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier MS-DLFSHB-01 High Wall Ductless Service Manual (04/2021), Table 9 notes p.17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.