Daikin · Mini-split troubleshooting

Discharge pipe thermistor disconnection control

FTXM-W/V

What is going on

Disconnection is found by comparing the discharge pipe temperature with the condensing temperature (outdoor in cooling, indoor in heating) after starting control and the detection timer. The compressor runs 9 minutes and then stops. If it repeats, the system shuts down. The error counter resets after 60 minutes of error-free running. The unit restarts after 3 minutes to check again.

Likely causes

  • Discharge pipe thermistor disconnected or reading wrong

Check in this order

  1. Check the discharge pipe thermistor connection and reading.
  2. Note the timer values for the model class when checking detection.

Applies to: Outdoor unit discharge pipe thermistor

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTXM-W/V service manual, p. 86. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.