Carrier · Mini-split troubleshooting
Discharge capacitors before troubleshooting
What is going on
Capacitors keep a charge after power is off. They must be discharged before any board work.
Check in this order
- Disconnect all power and lock out the unit.
- Discharge the electrolytic capacitor on the outdoor PCB.
- On other models, connect a discharge resistor (about 100 ohm, 40 W) or a soldering iron plug across the + and - terminals of the capacitor on the back of the outdoor PCB.
- Confirm the capacitor is discharged before touching the board.
- Wear anti-static gloves or a wrist strap when handling indoor or outdoor boards.
Applies to: Outdoor and indoor PCB
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FSOAH service manual, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.