Decommissioning and refrigerant recovery
What is going on
Steps for emptying a flammable refrigerant unit before it is removed or scrapped.
Check in this order
- Make sure you know the equipment well and have supervision for recovery.
- Isolate the system electrically. Power must be available before starting.
- Take an oil and refrigerant sample if analysis may be needed before reuse.
- Pump the system down if possible. If a vacuum is not possible, install a manifold to recover from several points.
- Place the recovery cylinder on scales before recovery.
- Use recovery equipment and cylinders rated for the refrigerant, and make sure the cylinder has a relief valve.
- Do not fill cylinders above 80% liquid volume or exceed their maximum working pressure.
- Do not mix refrigerants in recovery units or cylinders.
- Do not heat the compressor body with a flame to speed oil removal. Drain oil only after the compressor has been evacuated to an acceptable level.
- Label the equipment as decommissioned and emptied, with date and signature. Also label it as containing flammable refrigerant.
Applies to: D5FSCAH / D5FLCAH
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FSCAH/D5FLCAH service manual, p. 8-9. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.