Carrier · Mini-split troubleshooting

Cut, deburr, flare and connect refrigerant pipes

D5FCFA Ceiling/Floor Ductless

What is going on

Prepare the line set and connect it to the indoor unit first, then the outdoor unit.

Likely causes

  • Oblique, rough or warped cuts, and burrs left in the pipe, cause leaks.

Check in this order

  1. Measure the run between the indoor and outdoor units and cut the pipe a little longer than that.
  2. Cut at a true 90° angle without deforming the pipe.
  3. Ream or deburr the cut end fully. Hold the pipe pointing down so burrs do not fall in.
  4. Seal the pipe ends with PVC tape during handling.
  5. Slip the flare nuts on in the correct direction before flaring. They cannot be turned after flaring.
  6. Flare the pipe. The pipe end must stick out beyond the flare form. Check for cracks and an even flare.
  7. Lightly oil the flared surfaces with refrigeration oil.
  8. Connect the low-pressure line first, then the high-pressure line.
  9. Hand-tighten the nut, then torque it to the value in the torque table.
  10. Bend tubing no more than 90° and no more than 3 times, keeping the bend radius at least 3.9 in (10 mm).
  11. Keep the branch pipe horizontal. More than 10° of tilt can cause malfunction.
  12. Insulate the gas and liquid lines to prevent condensation.
  13. Keep the interconnect cable away from the copper tube.
  14. Do not connect the line set until both units are installed.

Applies to: Refrigerant line set installation

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FCFA installation manual, p. 20-21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.