Cut, deburr and flare refrigerant pipe

D5FSAAD5FLAA

What is going on

Prepare the copper line set for flare connections.

Check in this order

  1. Measure the distance between the indoor and outdoor units.
  2. Cut the pipe slightly longer than that distance with a pipe cutter, keeping the cut square at 90°.
  3. Deburr the cut end with a reamer or deburring tool, holding the pipe pointed downward so chips do not fall in.
  4. Seal the pipe ends with PVC tape until flaring.
  5. Slide flare nuts onto both ends facing the correct direction. Flaring makes this impossible to change later.
  6. Remove the tape, clamp the flare block so the pipe extends past the form, and turn the flaring tool clockwise until fully flared.
  7. Check the flare for cracks and even shape. Confirm it matches the dimensions in the flare table.

Applies to: Field-prepared refrigerant pipe ends

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FSAA and D5FLAA installation instructions, p. 24-25. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.