Connect refrigerant pipes and insulate

D5FSOAH

What is going on

Connect the low-pressure line first, then the high-pressure line. Do not let any other gas or substance enter the unit.

Check in this order

  1. Connect the copper pipes to the indoor unit first, then to the outdoor unit.
  2. Apply a thin coat of refrigeration oil to the flared ends.
  3. Align the centre of the two pipes, then tighten the flare nut by hand.
  4. Hold the unit tubing nut with a spanner and tighten the flare nut with a torque wrench to the value in the torque table.
  5. Bend the tubing gently at the middle. Do not exceed 90° or bend it more than 3 times. Minimum bend radius is 3.9 in (100 mm).
  6. Wrap the power cable, signal cable and piping together with binding tape. Do not twist the signal cable with other wiring.
  7. Thread the piping through the wall and connect it to the outdoor unit.
  8. Insulate all piping, including the outdoor unit valves. Bare pipe can cause burns or frostbite.
  9. Fix the water receiver (from the accessories box) to the indoor unit with a screw.
  10. Open the outdoor stop valves to let refrigerant flow between units.
  11. Check for leaks after installation. If a leak is found, ventilate the area immediately and evacuate the system.

Applies to: Refrigerant connections, 6K-18K

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FSOAH installation instructions, p. 20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.