Carrier · Mini-split troubleshooting
Compressor winding check
What is going on
Reference winding resistances for the inverter compressor models. Readings in the text are listed without a reliable column-to-row match, so verify against the manual figure before judging a winding. Values listed: 1.86 ohm, 0.75 ohm, 1.04 ohm, 0.65 ohm, 0.295 ohm. Compressor models: KSN140D58UFZ, KTF250D22UMT, KTM240D46UKT2, KTF310D43UMT, MTH550UKPC8FU. Winding pairs: Blue-Red, Blue-Black, Red-Black. Values are for reference only and may vary.
Check in this order
- Disconnect the compressor power cord from the outdoor PCB.
- Measure the resistance of each winding with a multimeter.
- Compare each reading with the matching compressor model in Table 8 and Tables 9 to 12.
- Replace the compressor if the readings are out of range.
Applies to: D5FSFAH outdoor unit compressor
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FSFAH service manual, p. 37. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.