Ceiling cassette panel installation
What is going on
Fit the one-way cassette panel into the ceiling opening and connect the display board.
Check in this order
- Cut the ceiling opening to 16.93 x 51.18 in (430 x 1300 mm), centred on the indoor unit body, and reinforce the ceiling if needed to avoid vibration.
- Remove the installation board after the ceiling is cut.
- Open the two screw covers and remove the two screws. Close the covers after the final screws are fixed.
- Open the air grille, push both latches to the middle to unlock it, and remove the panel grille.
- Secure the cassette panel to the one-way cassette with the two plastic straps.
- Rotate the louver by hand, then fix the panel with 3 x M4x22 screws and one ST3.9x16 screw.
- Open the covers on both sides of the panel and fix the rest of the M4x22 screws.
- Connect the display board to the main control board. Match the wire colours to the pins, and clip the wires to the strap.
- Install the control box cover, set the disconnect switch to ON, then close the side covers.
- Re-install the air grille by pushing the latches to lock, secure the two screws and close the covers.
Applies to: Cassette panel fitting for D5FSOAH indoor units
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FSOAH installation instructions, p. 21-22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.