Carrier · Mini-split troubleshooting

Buried refrigerant piping limits

D5FSOAH

What is going on

Buried line length is limited to prevent refrigerant migrating to a cold buried section and causing slugging at start-up.

Likely causes

  • Refrigerant migrates to cooler buried pipe during shutdown

Check in this order

  1. Do not bury more than 36 in. (914 mm) of refrigerant pipe.
  2. If any section is buried, provide a 6 in. (152 mm) vertical rise to the outdoor unit valve connections.

Applies to: Refrigerant piping

More mini-split guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FSOAH installation manual, p. 2. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.