Carrier · Mini-split troubleshooting
Buried refrigerant piping limits
What is going on
Buried line length is limited to prevent refrigerant migrating to a cold buried section and causing slugging at start-up.
Likely causes
- Refrigerant migrates to cooler buried pipe during shutdown
Check in this order
- Do not bury more than 36 in. (914 mm) of refrigerant pipe.
- If any section is buried, provide a 6 in. (152 mm) vertical rise to the outdoor unit valve connections.
Applies to: Refrigerant piping
More mini-split guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FSOAH installation manual, p. 2. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.