Working on flammable refrigerant circuits: area checks before work

D5FSFA

What is going on

Flammable refrigerant is used in this unit. Check the area before any work that opens the refrigerant circuit.

Check in this order

  1. Check the work area with a refrigerant detector suited to flammable refrigerants, before and during the work.
  2. Make sure the detector is not an ignition source. Never use a halide torch or any naked flame to look for leaks.
  3. Remove or put out all ignition sources and post NO SMOKING signs.
  4. Survey the area around the unit for flammable hazards.
  5. Make sure the area is open or well ventilated, and keep ventilation running during the work.
  6. Have a dry powder or CO2 fire extinguisher next to the charging area if any hot work is planned.
  7. Do not use any means to speed up defrosting or cleaning other than the manufacturer's methods.
  8. Do not pierce or burn the refrigerant tubing. Refrigerant may have no odor.

Applies to: D5FSFAH floor console ductless heat pump

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FSFAH service manual, p. 5-6. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.