Carrier · Heat pump troubleshooting

24K unit disassembly – panel removal

D5CURA

What is going on

Order for removing the outer panels on the 24K outdoor unit.

Check in this order

  1. Turn off the air conditioner and the power breaker.
  2. Remove the screw of the big handle, then remove the big handle (3 screws). One top cover screw sits under the big handle.
  3. Remove the top cover (3 screws, US models 3 screws).
  4. Remove the water collecting cover (2 screws).
  5. Remove the front panel (7 screws on on/off models, 9 screws on inverter models).
  6. Remove the right panel (5 screws).

Applies to: D5CURA 24K outdoor unit

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5CURA service manual, p. 68-70. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.