Carrier · Heat pump troubleshooting
18K unit disassembly – panel removal
What is going on
Order for removing the outer panels on the 18K outdoor unit.
Check in this order
- Turn off the air conditioner and the power breaker.
- Remove the screw of the big handle, then remove the big handle (3 screws). One top cover screw sits under the big handle.
- Remove the top cover (4 screws, US models 3 screws).
- Remove the water collecting cover (2 screws).
- Remove the front panel (7 screws on on/off models, 9 screws on inverter models).
- Remove the right panel (5 screws).
Applies to: D5CURA 18K outdoor unit
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5CURA service manual, p. 65-67. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.